KIWE-KOIE Series - Error Codes

These error codes are provided as a reference for the KIWE-KOIE Series system. The list below outlines common indoor unit (IDU) and outdoor unit (ODU) faults as defined in the service manual. Most issues should be inspected and confirmed by a licensed HVAC technician.

Error Code Table 

 Code Reason

E0

IDU & ODU Communication failure

E1

IDU Room Temperature sensor failure (IDU RT failure)

E2

IDU Coil temperature sensor failure (IDU IPT failure)

E3

ODU Coil temperature sensor failure (OPT)

E4

AC Cooling system abnormal

E5

IDU/ODU mismatched failure (especially performance test on the production line)

E6

IDU PG Fan motor / DC fan motor works abnormal (IDU failure)

E7

ODU Ambient Temperature sensor failure

E8

ODU Discharge Temperature sensor failure

E9

IPM / Compressor driving control abnormal

EA

ODU Current Test circuit failure

Eb

Communication abnormal of Main PCB and Display board (IDU failure)

EE

ODU EEPROM failure

EF

ODU DC fan motor failure

EH ODU suction temperature sensor failuture

EU

ODU Voltage test circuit abnormal

P0

IPM module protection

P1

Over / under voltage protection

P2

Over current protection

P4

ODU Discharge pipe over temperature protection

P5

Sub-cooling protection on Cooling mode

P6

Overheating protection on Cooling mode

P7

Overheating protection on Heating mode

P8

Outdoor over temperature / under temperature protection

P9

Compressor driving protection (Load abnormal)

PA

Communication failure for TOP flow unit / Preset mode conflict (IDU failure)

F0

Infrared customer feeling test sensor failure (IDU failure)

F1

Electric power test module failure (IDU failure)

F2

Discharge temperature sensor failure protection

F3

ODU coil temperature failure protection

F4

Cooling system gas flow abnormal

F5

PFC protection

F6

Compressor lack of phase / anti-phase protection

F7

IPM module temperature protection

F8

4-Way valve reversing abnormal

F9

Module temperature test circuit failure

FA

Compressor phase-current test circuit failure

Fb

Limiting/Reducing frequency for overload protection (Cooling/Heating mode)

FC

Limiting/Reducing frequency for high power consumption protection

FE

Limiting/Reducing frequency for module current protection (phase current of compressor)

FF

Limiting/Reducing frequency for module temperature protection

FH

Limiting/Reducing frequency for compressor driving protection

FP

Limiting/Reducing frequency for anti-condensation protection

FU

Limiting/Reducing frequency for anti-frost protection

Fj

Limiting/Reducing frequency for discharge over temperature protection

Fn

Limiting/Reducing frequency for ODU AC current protection

Fy

Gas leakage protection

bf

TVOC sensor failure (IDU failure, optional)

bc

PM2.5 sensor failure (IDU failure, optional)

bj

Humidity sensor failure (IDU failure)

CL

Filter duty remind

 


📄 Need the full technical manual?

Download the complete Error Code & Troubleshooting Guide (PDF) for detailed diagrams and advanced diagnostics.

👉 Download PDF


 

🔧 COMPLETE TROUBLESHOOTING FLOWS 

 

P0 — IPM Protection

Troubleshooting Flow

Restart unit → Works normally?

→ Yes → End

→ No → Continue

Check wiring connection (U/V/W)

→ Incorrect → Reconnect

 → P0 disappears?

  • Yes → End

  • No → Continue

→ Correct → Continue

Can compressor start?

→ No → Continue

 Test voltage between U/V/W–G (DC 20–200V)

 → No voltage → Replace ODU PCB

 → Voltage present → Replace compressor → End

→ Yes → Continue

Outdoor fan motor slow or not working?

→ Yes → Replace ODU fan motor

 → Works normal?

  • Yes → End

  • No → Continue

→ No → Continue

AC pressure correct?

(Cooling: 116–189 psi | Heating: 290–522 psi)

→ No → Continue

 Condenser / evaporator dirty?

 → Yes: Clean

  → Unit works?

   • Yes → End

   • No → Continue

 Capillary blocked?

 → Yes: Replace capillary

  → P0 disappears?

   • Yes → End

→ Yes → Continue

Turn unit ON and check again

→ Issue resolved?

 • Yes → End

 • No → Replace compressor → End


 

P1 — Over / Under Voltage Protection

Troubleshooting Flow

Power supply between 145–260V?

→ No: Wait until voltage stabilizes

 → P1 disappears?

  • Yes → End

  • No → Continue

→ Yes → Continue

Busbar voltage between 150–420V?

→ No: Wait until recovery

 → Unit works?

  • Yes → End

  • No → Continue

→ Yes → Continue

Replace ODU PCB → End


P2 — Over Current Protection

Troubleshooting Flow

Indoor fan motor working?

→ No: Replace fan motor

 → P2 disappears?

  • Yes → End

  • No → Continue

→ Yes → Continue

Indoor filter or outdoor condenser dirty?

→ Yes: Clean

→ No → Continue

Restart unit

→ P2 disappears?

 • Yes → End

 • No → Replace ODU PCB → End


P5 — Sub-Cooling Protection (Cooling/Dry Mode)

Troubleshooting Flow

Wait a few minutes → P5 still displayed?

→ No → Normal → End

→ Yes → Continue

Indoor filter dirty?

→ Yes: Clean filter

 → P5 disappears?

  • Yes → End

  • No → Continue

→ No → Continue

Air inlet blocked?

→ Yes: Clear blockage

 → P5 disappears?

  • Yes → End

  • No → Continue

→ No → Continue

Fan blade rotates freely?

→ No: Repair/adjust

 → P5 disappears?

  • Yes → End

  • No → Continue

→ Yes → Continue

Fan motor slow or stopped?

→ Yes → Check motor

 → Defective → Replace motor

  → P5 disappears?

   • Yes → End

→ No → Continue

Sensor (IPT) abnormal?

→ Yes: Replace sensor → End

→ No → Replace IDU PCB → End


P6 — Overheating Protection (Cooling Mode)

Troubleshooting Flow

Indoor fan motor working normally?

→ No → Check motor

 → Faulty → Replace

  → P6 disappears?

   • Yes → End

→ Yes → Continue

Sensor loose from connector?

→ Yes: Reconnect

 → P6 disappears?

  • Yes → End

  • No → Continue

→ No → Continue

Sensor open or short circuit?

→ Yes: Replace OPT sensor

 → P6 disappears?

  • Yes → End

  • No → Continue

→ No → Continue

Replace ODU PCB → End


P7 — Overheating Protection (Heating Mode)

Troubleshooting Flow

Outdoor fan motor working normally?

→ No → Check motor

 → Faulty → Replace

  → P7 disappears?

   • Yes → End

→ Yes → Continue

Sensor loose from connector?

→ Yes: Reconnect

 → P7 disappears?

  • Yes → End

  • No → Continue

→ No → Continue

Sensor open or short circuit?

→ Yes: Replace IPT sensor

 → P7 disappears?

  • Yes → End

  • No → Continue

→ No → Continue

Replace IDU PCB → End


P8 — Outdoor Over / Under Temperature Protection

Troubleshooting Flow

Ambient temperature within specification?

→ No → Wait until normal

→ Yes → Continue

Enough space for outdoor ventilation?

→ No: Relocate outdoor unit

 → P8 disappears?

  • Yes → End

  • No → Continue

→ Yes → Continue

Sensor open or short circuit?

→ Yes: Replace OAT sensor

 → P8 disappears?

  • Yes → End

  • No → Continue

→ No → Continue

Replace ODU PCB → End


P9 — Compressor Driving Protection

Troubleshooting Flow

Compressor wiring (U/V/W) correct?

→ No: Correct wiring

 → Still P9?

  • No → End

  • Yes → Continue

→ Yes → Continue

Unit starts < 3 minutes then stops?

→ Yes: Normal protection → Restart after 3 min

 → Still P9?

  • No → End

  • Yes → Continue

→ No → Continue

Compressor stops immediately after start?

→ Yes: Replace ODU PCB → End


 

F4 — Cooling System Gas Flow Abnormal

Check 2-way & 3-way valves open?

→ No: Open valves

 → F4 disappears?

  • Yes → End

  • No → Continue

→ Yes → Continue

IPT sensor open or short?

→ Yes: Replace sensor → End


F5 — PFC Protection

F5 appears randomly?

→ Yes: Check power supply

 → Still F5?

  • No → End

  • Yes → Continue

→ No → Continue

Turn OFF unit for 3 minutes → Restart

→ Still F5?

 • Yes → Replace ODU PCB → End

 • No → End


F6 — Compressor Phase Protection

Check wiring → Fix if needed

Check wire condition → Replace if bad

Check phase sequence → Swap wires

Measure resistance (U/V/W)

→ Not equal → Replace compressor

Measure resistance to copper pipe

→ ≤500Ω → Replace compressor

Otherwise → Replace ODU PCB


F7 — Module Temperature Protection

Check IPM contact / screws / dust

Check system pressure & airflow

Check valves / capillary / coils

If unresolved → Replace ODU PCB


F8 — 4-Way Valve Abnormal

Check wiring → Fix

Check voltage → Test coil

Replace coil if faulty

If unresolved → Replace ODU PCB


Fy — Gas Leakage Protection 

Check piping for leakage

→ Yes: Repair + recharge

 → Problem solved?

  • Yes → End

  • No → Replace IDU PCB → End

→ No → Continue

Check temp difference (RT vs IPT after 10 min)

→ ≤2°C → Continue

 Evaporator pipe blocked?

 → Yes: Replace evaporator

  → Problem solved?

   • Yes → End

→ >2°C → Continue

Sensor connected properly?

→ No: Reconnect

Sensor open/short?

→ Yes: Replace

If still issue → Replace IDU PCB → End


CL — Filter Duty Reminder

Check air filter dirty

→ Yes: Clean

Turn OFF and ON power

→ End

Need help? Need help?